Liebert iCOM User Menu Screens

User menus report general cooling unit operations and status. The user menu password is 1490. To
review the full User Menu, refer to Figure 54.
The User menu parameter tables in this document may differ from the display on some cooling units.
The Liebert iCOM functions with several Liebert Thermal Management units, each with its own set
of controls. In addition, the Liebert iCOM firmware is being updated constantly. As a result, the User
menu parameter tables in this manual may differ from the display on a cooling unit. Check
www.liebert.com
Setpoints Parameters

Figure 71 User Menus-Setpoints parameters screen

USER MENUS
°C / °F
% RH
SET
U102 Controlling Sensor—Allows the user to select which sensor will be used to determine the
amount of cooling needed. This parameter can select only a single sensor for both the temperature
and fan speed control. Use the Service / Setpoints menu to decouple the operation of fan speed to the
remote sensors and the cooling capacity to the supply sensor.
U103 Temperature Setpoint—Allows selecting a temperature that the cooling unit will maintain
by applying cooling and or reheats.
U104 Humidity Setpoint—Allows selecting a humidity that the cooling unit will maintain by
removing or adding moisture to the air.
Spare Parts List
Spare Parts—The spare parts lists contains a detailed description and part number that can be used
to order parts for the unit. These part numbers are specific to each model and option installed on the
unit.
®