External Connections - Omron SYSMAC CS1 Operation Manual

Hide thumbs Also See for SYSMAC CS1:
Table of Contents

Advertisement

External Connections

1, 2, 3...
2-5

External Connections

Note We assume that one Memory Card will be installed in the Board and used as
ROM.
1. Align the Memory Card with its label facing up and insert it into the Memory
Card slot.
2. Press the Memory Card firmly so that it is inserted all the way into the slot.
This section describes how to connect external devices such as Expansion
Racks, DeviceNet Slaves, CompoBus/S Slaves, and Programming Devices to
the SYSMAC CS1 Board.
Note
1. Turn the power supply OFF to the CS1 Board and all Slaves, and turn OFF
the communications power supply before connecting communications
cables.
2. Tighten the screws holding the cables to the DeviceNet connectors to a
torque of 0.5 NSm.
3. Be sure to confirm that the terminal blocks, expansion cables, and other
items with locking devices are properly locked into place.
4. Do not pull on the communications cables.
5. Do not forcibly bend the communications cables.
6. Do not place objects on the communications cables.
7. Always use crimp terminals when connecting communications cables. Con-
necting bare twisted wires can result in disconnection, broken wires, faulty
operation, or damage to the product.
8. Use an appropriate crimp tool and appropriate methods to attach the crimp
terminals. Consult the manufacturer of the crimp tool for specific instruc-
tions. Inappropriate crimp tools or crimping methods can result in broken
wires.
Section
2-5
Press.
41

Advertisement

Table of Contents
loading