Dunkirk XEB-2 Installation Instructions Manual page 5

Gas-fired hot water induced craft boilers
Table of Contents

Advertisement

I Provision forcombustion andventilationairmustbein accordance w ithSection 53, AirforCombustion andVentilation, of
theNational f uelGas Code,ANSIZ223.1-1atest revision, orapplicable p rovisions o fthelocalbuilding codes.
I
WARNING
Be sure provide enough fresh air for combustion.
Enough
air insures
proper combustion
and
assures
that hazard will develop
due to the
lack oxygen.
NOTE
If you use a fireplace or a kitchen or bathroom
exhaust fan, you should install an outside air
intake. These
devices will rob the boiler and
water heater of combustion
air.
You must provide for enough fresh air to assure
proper
combustion.
The fire in the boiler uses
oxygen. It must have a continuous
supply. The air
in a house contains only enough oxygen to supply
the burner for a short time. Outside air must enter
the house to replace that used by the burner. Study
following examples 1 and 2 to determine your fresh
air requirements.
EXAMPLE 1: Boiler Located in Unconfined Space
An unconfined space is defined as a space whose
volume
is not less than 50 cubic feet per 1,000
Btu per hour of the total input rating of all appliances
installed in that space.
If your boiler is in an open area (unpartitioned
basement)
in a conventional
house, the air that
leaks
through
the cracks
around
doors
and
windows
will usually be adequate
to provide air
for combustion.
The doors should not fit .tightly.
Do not caulk
the cracks
around
the windows.
Equipment
located in buildings
of unusually
tight
construction
shall
be provided
with
air for
combustion,
ventilation,
and dilution of flue gases
using the methods
described
in example
2B or
shall be specially engineered. The authority having
jurisdiction
must approve
specially
engineered
installations.
EXAMPLE
2: Boiler Located in Confined
Space
A. All Air from Inside the Building: The confined
space
shall
be provided
with two permanent
openings communicating
directlywith
an additional
room(s) of sufficient volume so that the combined
volume
of all spaces
meets
the criteria
for an
unconfined
space.
The total
input
of all gas
utilization equipment
installed in the
combined space shall be considered in making this
determination.
Each
opening
shall
have
a
minimumfree
area of one square inch per 1,000 Btu
per hour of the total input rating of all gas utilization
equipment in the confined space, but not less that
100 square inches. One opening shall be within 12
inches of the top and one within 12 inches of the
bottom of the enclosure. The minimum dimension of
air openings shall not be less than 3 inches.
B. All Air from
Outdoors:
The confined space
shall communicate
with the outdoors in accordance
with methods
1 or 2. The minimum dimension
of
air openings
shall not be less than 3 in. Where
ducts are used, they shall be of the same cross-
sectional
area as the free area of the openings to
which they connect.
1.Two permanent
openings,
one commencing
within 12 inches of the top, and one commencing
within 12 inches of the bottom, of the enclosure
shall
be provided.
The
openings
shall
communicate
directly, or by the ducts, with the
outdoors or spaces (crawl or attic) that freely
communicate
with the outdoors.
a) Where
directly
communicating
with the
outdoors
or where communicating
to the
outdoors
through
vertical
ducts,
each
opening shall have a minimum free area of
1 sq. in, per 4000 Btu per hour of total input
rating of all equipment
in the enclosure.
(See Figure 3A.)
b) Where
communicating
with the outdoors
throughhorizontal
ducts, each opening shall
have a minimum free area of 1 area of sq.
in. per 2000 Btu per hour of total rating of
all equipment in the enclosure. (See Fig.3B.)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xeb-3Xeb-6Xeb-7Xeb-4Xeb-5

Table of Contents