GAS VALVE SAFETY SHUTDOWN
TEST
With main burners firing, disconnect the ignition cable
from the intermittent pilot control box. The gas valve
should
shut off the main burners.
TURN
OFF
ELECTRIC
POWER to boiler before reconnecting
ignition cable, to prevent electric shock.
ADJUST
PILOT BURNER
1. Remove screw cover over pilot adjusting screw.
2. Insert small screwdriver and adjust flame as needed.
(Fig. 14). Turn screw counterclockwise
to increase
flame, clockwise to decrease (Fig. 15).
3. Replace screw cover over pilot adjusting screw.
MAIN BURNER(S)
The main
burners
do not require primary
air
adjustment and are not equipped with primary air
shutters.
Main burner flames
should form sharp
blue inner cones in a softer blue outer mantel, with
no yellow. Puffs of air from blowing on the flame or
stamping on the floor will cause the flames to turn
orange momentarily.
This is not unusual.
Remain
still when observing
the main burner flames. If the
flame appearance
is not correct, check main burner
orifices and the burner throat and flame ports for
dust and lint obstruction.
It may be necessary
to
remove the rollout shield to observe the main burner
flames.
Replace
rollout shield after observation.
Refer to Figure 16.
ADJUST LIMIT CONTROLS
Instructions for each control are included with the controls
to see
if it shuts
off the gas
supply
to the
burners.Turn
your thermostat
up to call for heat
and let your boiler run until the temperature
of the
water reaches the limit setting. The gas valve should
shut off and the circulator keep running until the
thermostat
is satisfied,
or the water cools enough
to restart the burners through the limit control.
To check the operation
of the contacts
in the
pressure
switch,
disconnect
the rubber
tubing
(located
between
the blower
and the pressure
switch) from the pressure switch, while the boiler
is operating.
The burners should extinguish
and
the blower should keep running. When the tubing
is reconnected
to the pressure switch, the ignition
sequence
should begin, resulting in ignition of the
main burners.
Finally,
set
the thermostat
for the desired
temperature.
Special conditions in your home and
the location of the thermostat will govern this setting.
Safe lighting and other performance
criteria were
met with the gas manifold
and control assembly
provided on the boiler when the boiler underwent
tests specified
in ANSI Z21.13-latest
revision.
f
l
Flame
on sensor
RECOMMENDED BOILER WATER TEMPERATURES
Tvoe of Heatina Unit
Limit Control
Settina
Standing Radiators.............................................180°F
Baseboard and Convector Radiators ..............200 ° F.
These settings can be changed after you have had
some idea how the system works. Example: If your
system does not give quite enough heat in very cold
weather, you can raise the limit setting to 220 ° F.
ADJUST THERMOSTAT HEAT ANTICIPATOR
INSTRUCTIONS
FOR THE FINALADJUSTMENT
OF THE THERMOSTAT
ARE PACKAGED
WITH
THE THERMOSTAT.
Set Heat anticipator
at .2.
Check
thermostat
operation.
When
set above
temperature
indicated
on the thermometer,
boiler
burners should ignite. Make certain the thermostat
turns off the boiler when room temperature
reaches
the selected setting and starts the boiler operating
when
room
temperature
falls
a few degrees.
Aftersetting
limit control to desired setting, check
24
[k'E:;SJ
[c ]JL
[ I
(
[ I[ [ [
_liNl_[ B? (,d _ S([_ff _,v ¸ )

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xeb-3Xeb-6Xeb-7Xeb-4Xeb-5

Table of Contents