WATER TEMPERATURE CONTROL
The water temperature
limit control in the relay is
adjustable
and may be set as necessary.
It may
be set as low as 140 ° F, or as high as 240 ° F This
depends
on the type and amount
of radiation
involved and weather conditions.
CIRCULATING PUMP
Every
Forced
Hot-Water
System
requires
a
Circulating Pump. A separate pump or zone valve is
required for each Zone, if you have a two or more
Zone System. This pump must have the capacity to
provide the circulation required by your system.
The pump does not come pre-installed on the boiler.
It must be connected
to the circulator
harness in
the field according
to the pump manufacturer's
instructions and the wiring diagrams in this manual.
BLOWER (DRAFT INDUCER)
The blower provides a means for pulling air through
the boiler and exhausting
the flue gasses into the
vent system. The blower shuts offwhen the burners
are not firing. This keeps heat in the house rather
than having it go up the chimney.
PRESSURE SWITCH
The air pressure
switch
works
on a negative
pressure. When the blower comes on the air
pressure switch operates the intermittent
pilot and
gas valve. The air pressure
switch is factory set
and will only work when
the blower
operates
properly.
It will not allow the boiler to come on if
the blower does not generate enough pressure or
if the venting system is blocked.
FACTORY PRESSURE
SWITCH SETPOINT:
-0.4" wc. for 2-5 section boilers.
-0.5" w.c. for 6-7 section boilers.
ROLLOUT
SWITCH
(FLAME
ROLLOUT
SAFETY
SHUTOFF)
The rollout switch is a temperature-sensitive
fuse
link device.
It is located
on the boiler base just
outside the fire box. In the event of heat exchanger
flueway blockage
causing flame to roll out of the
fire box, the fuse will blow, shutting down the flow
of gas to the main burners.
The fuse does not
change in appearance
when blown,
If the rollout switch blows, it must be replaced with
an exact
replacement.
Check
heat exchanger
flueways
for blockage
when restoring
system to
operating condition. Do not operate system without
a rollout switch.