Cautions On Using Transparent Function By Way Of Usb In Got1000 Series - Mitsubishi FX3U-?*MR/ES User Manual

Fx3u series programmable controllers
Table of Contents

Advertisement

FX
Series Programmable Controllers
3U
User's Manual - Hardware Edition
5.3
Cautions on using transparent function by way of USB in GOT1000
Series
When monitoring circuits, device registration, etc. or reading/writing programs in an FX
Developer Ver. 8.22Y or later using the transparent function by way of USB in the GOT1000 Series, make
sure to execute the following setting.
If the following setting is not provided, a communication error occurs.
When using transparent function by way of
USB in GOT1000 Series
When using transparent function by way of
RS-232 in GOT1000 Series
When directly connecting GX Developer to
PLC
*1.
GX Developer Ver. 8.24A or later supports the FX
Setting in GX Developer (Ver. 8.22Y or later)
1
Select [Online] → [Transfer setup...] to open the "Transfer setup" dialog box.
2
Double-click [Serial] in [PC side I/F] to open the "PC side I/F Serial setting"
dialog box.
3
Select "USB (GOT Transparent mode)".
4
Click the [OK] button to finish the setting.
84

5.3 Cautions on using transparent function by way of USB in GOT1000 Series

GX Developer Ver. 8.21X or former
Not supported (not available)
Set "COM port" and "Transmission
speed" on "PC side I/F Serial setting"
dialog box.
Double-click it.
5 Version Information and Peripheral Equipment Connectability
Select "RS-232C" in setting shown
below, and set "COM port" and
"Transmission speed".
Series.
3U
Select "USB (GOT
transparent mode)"
PLC from GX
3U
GX Developer Ver. 8.22Y or later
Setting shown below is required.
*1