Fx-16Eyt-Tb, Fx-16Eyt-H-Tb; Specifications - Mitsubishi FX3U-?*MR/ES User Manual

Fx3u series programmable controllers
Table of Contents

Advertisement

FX
Series Programmable Controllers
3U
User's Manual - Hardware Edition
20.8

FX-16EYT-TB, FX-16EYT-H-TB

The FX-16EYT(-H)-TB is available by connecting it to a FX
Connectable models FX
The applications shown below are not supported.
Pulse Y output (PLSY) instruction, acceleration/deceleration setup (PLSR) instruction, pulse width
modulation (PWM) instruction, DOG search zero return (DSZR) instruction, interruption positioning
Pulse
(DVIT) instruction, batch data positioning mode (TBL) instruction, absolute current value read (ABS)
outputs
instruction, zero return (ZRN) instruction, variable speed pulse output (PLSV) instruction, drive to
increment (DRVI) instruction, drive to absolute (DRVA) instruction
Time division
Input matrix (MTR) instruction, hexadecimal input (HKY) instruction, digital switch (DSW) instruction,
input
arrow switch (ARWS) instruction
Time division
Seven segment with latch (SEGL) instruction, print (ASCII Code) (PR) instruction
output

20.8.1 Specifications

Item
Input/output circuitry
Load voltage
Resistance
load
Max. load
Inductive
load
Open-circuit leakage
current
OFF→ON
Response
*1
time
ON→OFF
Output element's ON
voltage
Circuit isolation
Operation indicators
Power consumption
*1.
This response time does not include the response delay of the PLC.
456
Output Connector
-16EYT-C (sink output)
2N
FX-16EYT-TB
Photo-
3.3kΩ
coupler
24+
LED
CN1
24V DC
Connector
7mA
side
5 to 30V DC
0.5 A / point
The total load current of resistance loads per
common terminal should be the following value:
• 4 output points/common terminal: 0.8A or less
12 W/24V DC
0.1 mA / 30V DC
*1
0.2 ms or less / 24V DC
*1
1.5 ms or less / 24V DC
1.5 V
Photo-coupler isolation
LED is lit when photo-coupler power is supplied LED is lit when photo-coupler power is supplied
2.7 W (112 mA 24V DC)
series output extension block (transistor).
2N
Unsupported Applications
Transistor output
Fuse
0 to 7
24+
5 to 30V
CN1
DC
Connector
COMn
side
External
wiring
The total load current of resistance loads per
common terminal should be the following value:
• 4 output points/common terminal: 3A or less
20 FX-16/32E*-*-TB (Terminal Block)
20.8 FX-16EYT-TB, FX-16EYT-H-TB
FX-16EYT-H-TB
Photo-
3.3kΩ
0 to 7
coupler
LED
24V DC
7mA
COMn
5 to 30V DC
1 A / point
24 W/24V DC
0.1 mA / 30V DC
0.3 ms or less / 24V DC
4 ms or less / 24V DC
1.5 V
Photo-coupler isolation
2.7 W (112 mA 24V DC)
Fuse
5 to 30V
DC
External
wiring

Advertisement

Table of Contents
loading

Table of Contents