Fx 2N -8Er (24V Dc Sink Input, Relay Output); Product Specifications - Mitsubishi FX3U-?*MR/ES User Manual

Fx3u series programmable controllers
Table of Contents

Advertisement

FX
Series Programmable Controllers
3U
User's Manual - Hardware Edition
16.3
FX
-8ER (24V DC Sink Input, Relay Output)
2N

16.3.1 Product specifications

The generic specifications are identical to the main unit specifications.
For external wiring, refer to the following chapters.
1. Power supply specifications
Item
Product type
Rated voltage
2. Weight and Other specifications
Item
MASS (Weight)
Other
3. Input specifications
Item
Input points
Connection unit
Input type
Input signal voltage
Input signal current
Input impedance
Input-ON
current
Input sensitivity
current
Input-OFF
current
Input response time
Input signal type
Input circuit insulation
Indication of input operation
Input circuit diagram
→ Refer to Section 4.1 for generic specifications.
24V DC (supplied from main unit and input/output powered extension unit)
• The extension cable is already connected to the extension block.
• Accessories: Label for indication of input/output number
• The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
Vertical terminal block (M3 screws) / For a detailed description of wiring, refer to
the input line connection diagram of the main unit.
3.5 mA or more at 24V DC
No-voltage contact input
NPN open collector transistor
Photo-coupler insulation
LED on panel lights when input.
Sink input line
connection
Main unit
16 FX2N-8/16E*-*(Input/Output Extension Blocks)
16.3 FX2N-8ER (24V DC Sink Input, Relay Output)
→ Refer to Chapter 10 for input wiring.
→ Refer to Chapter 12 for output wiring.
FX
-8ER
2N
FX
extension block
2N
FX
-8ER
2N
0.2 kg (0.44lbs)
FX
-8ER
2N
4 points
Sink
24V DC ± 10%
5 mA/24V DC
4.3kΩ
1.5 mA or less
Approx. 10 ms
S/S
0V
24V
24+
X
4.3kΩ
11
12
13
14
15
16
17
18
19
20
321