Low Battery Disconnect - Outback Power Systems MX60 Installation, Programming, And User's Manual

Maximum power point tracking charge controller
Hide thumbs Also See for MX60:
Table of Contents

Advertisement

AUX MODE
Diversion
Off
EXIT NEXT TIME VOLT
AUX MODE
Low Batt Disconnect
On
EXIT NEXT TIME VOLT
Delay
Time
01
BACK
-
+
OutBack Power Systems Inc.
Press the <NEXT> soft key to view the Low Batt(ery)
Disconnect screen.
When the battery voltage falls below the disconnect
volts, the AUX connected loads only are disconnected;
the loads are On when the battery voltage rises
above the reconnect volts. To adjust these set points,
press the <TIME> and <VOLT> soft keys.
Press either the < - > or < + > soft key to adjust the
Sec
delay time. This is the time period the MX60 waits
Timer
before either activating or deactivating the AUX
001
MODE when either the disconnect or reconnect volt-
ages are reached. When the low voltage occurs, the
timer shows the seconds remaining before discon-
necting. When the reconnect voltage is reached, the
timer shows the userdetermined time before con-
necting. Press the <BACK> soft key to return to the
Low Batt Disconnect screen.