Outback Power Systems MX60 Installation, Programming, And User's Manual page 55

Maximum power point tracking charge controller
Hide thumbs Also See for MX60:
Table of Contents

Advertisement

To adjust these values and enhance the performance of these systems, use the MX60 ADVANCED
MENU to make changes. To determine your micro-hydro or fuel cell system's best settings for MPP
voltage, do the following:
1. Use Auto Sweep and record the watts yielded. This value should be in line with your generator
capacity.
2. Switch to U-Pick % Voc mode and input diff erent Park Mpp percentage values, checking the
watts value for each. This will require some experimentation.
• The MX60 can operate at any of the following fi xed percentages, selected in the" Park Mpp"
screen in the ADVANCED MENU selection:
40%, 50%, 67%, 70%, 72%, 75%, 76%, 77%, 78%, 80%, 81%, 83% or 85% of the measured
open circuit voltage
• The user will have to experiment with each of the 13 fi xed percentage values to
determine an appropriate fi xed percentage value. Typical fi xed values between 67% up to
78% have provided optimal results; however, each system is diff erent and these fi xed
percentage values should be used as guidelines only
3. Compare the Auto Sweep and U-Pick % Voc values and determine which will best fi t
your system.
In addition to establishing the best mode and percentage values for determining the MPP voltage,
a user can also adjust the sweep interval and the range of values the MX60 uses to search for the
MPP voltage.
(If necessary, re-enter the system password 141 at any point while optimizing the
system's performance.)