NOTES
• An optional battery Remote Temperature Sensor (RTS) is recommended for accurate
battery recharging (only one RTS is needed for multiple OutBack Series Inverter/Chargers
and MX60 units when an OutBack HUB and a MATE are parts of the system). When one RTS
is used, it must be connected to the component plugged into the Port 1 of the HUB.
• AUX modes include powering a relay, LED indicator, and Piezo-buzzer or brushless fan.
• The OutBack MATE can display a single MX60 or multiple MX60s if connected to a HUB.
• Surge protection on the input (PV) side of the MX60 and on the battery side is required for
extended warranty protection. A dwelling rooftop array requires ground fault protection
(OutBack OBDC-GFP/2 recommended).
• Always install the MX60 in an upright position. The MX60 must be secured for a safe
installation and to retain warranty protection. Use a 1 5/8" wood screw through the slotted
hole at the top of the MX60 and at least two screws in the internally located holes at the
bottom of the MX60's enclosure.