CHARGER SETUP

This screen allows changes to the MX60's recharging voltage set points (Current Limit,
Absorb, Float):
• The presently selected numerical value will have an asterisk " * " to the left of it.
• Pressing " " selects the value to be changed.
• You may need to re-enter the password to change these settings.
• The default charger output current limit setting is 60 amps and is adjustable up to 70 amps. At
70 amps, a 70A or 80A breaker must be used between the battery and the MX60.
• Change Absorb and Float set points using this screen if the battery manufacturer's recommen-
dations are diff erent than the default values. Otherwise, see page 79 for suggested recharging
voltage set points.
• If a battery remote temperature sensor (RTS) is used, its compensated voltage values can be
viewed in the MISCELLANEOUS (Misc) screen under the Tmp Comp heading.
LIMIT
ABSORB
Amps
Volts
*60.0
14.4
EXIT
-
OutBack Power Systems Inc.
Please Note: If an RTS is used, set the ABSORB
FLOAT
and FLOAT setting voltage based on a 25°C / 77°F
Volts
13.6
setting. These are typically the manufacturer's set
+
points (always consult the battery manufacturer's
recommendations). If an RTS is not in use, please
see the Non-Battery Temperature Compensated
System values (page 85) and adjust the ABSORB/
FLOAT values accordingly.