© 2016 GE Multilin Inc. All rights reserved.
The MM300 Motor Management System Instruction Manual for revision 1.6x.
MM300 Motor Management System, EnerVista, EnerVista Launchpad, and EnerVista
MM300 Setup are registered trademarks of GE Multilin Inc.
Allen-Bradley, RSLinx DeviceNet-3, RSNetWorx for DeviceNet, EDS Wizard, Allen-Bradley
1770-KFD Driver, and 1747-SDN Scanner Module, are registered trademarks of Rockwell
Automation, Inc.
The following screens are captured from ProfiCaptain v1.0 - © 2005 Profibus Center,
Netherlands:
– Figure 2 - Profibus configuration menu
– Figure 3 - Profibus I/O data - 87 words in, 1 word out
– Figure 4 - Profibus configuration menu
– Figure 5 - Profibus I/O data - 3 words in, 1 word out
The following screens are captured from ProfiTrace v1.4 - © 2005 Profibus Center,
Netherlands:
– Figure 6 - Profibus - extended diagnostic data
– Figure 7 - Profibus - no extended diagnostic data
The following screen is captured from DeviceNet Master Simulator. HMS Industrial
Networks. Version 1.7.4. ©2001, Bihl+Wiedemann GmbH
– Figure 8 - DeviceNet polled I/O data
The contents of this manual are the property of GE Multilin Inc. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin. The content of this manual is for informational use only and is subject to
change without notice.
Part number: 1601-9025-A9 (February 2016)
Need help?
Do you have a question about the MM300 and is the answer not in the manual?
Questions and answers
we have a problem with device MM300. it says that the device is invalid through the software and does not read the device. the communication is through RS 485. is it possible to give us an advice or send us some reccomendations or instructions?
For a GE MM300 device that is not recognized by software and communicates via RS485, follow these troubleshooting steps:
1. Ensure correct RS485 wiring:
- Use two-wire RS485 in a daisy chain configuration.
- Install a 120 Ohm resistor in series with a 1 nF ceramic capacitor at each end of the link.
- Use shielded wire and ground the shield at only one location.
2. Check device addressing and termination:
- Confirm proper device address and ensure no address conflicts.
- Verify that termination networks are correctly installed at both ends.
3. Confirm half-duplex communication:
- Ensure that the system supports half-duplex communication and not sending and receiving data simultaneously.
4. If using USB for setup (e.g., USB-to-RS485 converter) and the device is not recognized:
- Repeat the connection procedure 2–3 times.
- If still not recognized, uninstall the USB driver from Device Manager under modems.
- Disconnect the USB cable, wait at least 10 seconds, then reconnect.
- When prompted by the Hardware Wizard, select "No, not this time," then "Install the software automatically," and press "Continue Anyway."
- Finish the installation and check if the USB device appears in the setup software.
These steps help ensure proper hardware connection and correct software recognition of the MM300 device.