GE MM300 Manual page 152

Motor management system/low voltage motor protection and control
Hide thumbs Also See for MM300:
Table of Contents

Advertisement

DEVICENET PROTOCOL
4–74
ATTRIBUTE
Motor Statistics
0D
H
Cause of Trip
0E
H
Last trip date and time
0F
H
Last pre-trip currents
10
H
Last pre-trip motor load
11
H
Last pre-trip line voltages
12
H
Last pre-trip phase voltages
13
H
Last pre-trip frequency
14
H
Last pre-trip power
15
H
Trip diagnostic data
16
H
Alarm diagnostic data
17
H
Start block status data
18
H
ITEM DESCRIPTION
Number of Motor Starts
Number of UV Restarts
Motor Running Hours
Cause of Last Trip
Time of Last Trip
Date of Last Trip
Pre Trip Ia
Pre Trip Ib
Pre Trip Ic
Pre Trip Igrd
Pre Trip Motor Load
Pre Trip Current Unbalance
Pre Trip Vab
Pre Trip Vbc
Pre Trip Vca
Pre Trip Van
Pre Trip Vbn
Pre Trip Vcn
Pre Trip System Frequency
Pre Trip Real Power
Pre Trip Reactive Power
Pre Trip Apparent Power
Pre Trip Power Factor
Trip Status 3
Trip Status 2
Trip Status 1
Alarm Status 3
Alarm Status 2
Alarm Status 1
Reserved
Start Timer 1
Start Timer 2
Start Timer 3
Start Timer 4
Start Timer 5
MM300 MOTOR MANAGEMENT SYSTEM – COMMUNICATIONS GUIDE
CHAPTER 4: FIELDBUS INTERFACE
SIZE IN
FORMAT
BYTES
2
F1
2
F1
4
F9
2
FC134
4
F19
4
F18
4
F10
4
F10
4
F10
4
F10
2
F3
2
F1
2
F1
2
F1
2
F1
2
F1
2
F1
2
F1
2
F3
4
F13
4
F13
2
F2
2
F21
4
FC185
4
FC184
4
FC183
4
FC181
4
FC180
4
FC179
2
F1
2
F1
2
F1
2
F1
2
F1
2
F1

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MM300 and is the answer not in the manual?

Questions and answers

Kristiyan
March 31, 2025

we have a problem with device MM300. it says that the device is invalid through the software and does not read the device. the communication is through RS 485. is it possible to give us an advice or send us some reccomendations or instructions?

1 comments:
Mr. Anderson
March 31, 2025

For a GE MM300 device that is not recognized by software and communicates via RS485, follow these troubleshooting steps:

1. Ensure correct RS485 wiring:
- Use two-wire RS485 in a daisy chain configuration.
- Install a 120 Ohm resistor in series with a 1 nF ceramic capacitor at each end of the link.
- Use shielded wire and ground the shield at only one location.

2. Check device addressing and termination:
- Confirm proper device address and ensure no address conflicts.
- Verify that termination networks are correctly installed at both ends.

3. Confirm half-duplex communication:
- Ensure that the system supports half-duplex communication and not sending and receiving data simultaneously.

4. If using USB for setup (e.g., USB-to-RS485 converter) and the device is not recognized:
- Repeat the connection procedure 2–3 times.
- If still not recognized, uninstall the USB driver from Device Manager under modems.
- Disconnect the USB cable, wait at least 10 seconds, then reconnect.
- When prompted by the Hardware Wizard, select "No, not this time," then "Install the software automatically," and press "Continue Anyway."
- Finish the installation and check if the USB device appears in the setup software.

These steps help ensure proper hardware connection and correct software recognition of the MM300 device.

This answer is automatically generated