Omron I537-E2-01 User Manual page 102

Table of Contents

Advertisement

Jump Frequencies: d3
Name
Parame-
terNum-
LCD
ber
Display
Jump fre-
quency 1
d3-01
Set the center values of the jump
Jump Freq 1
frequencies in Hz.
This function is disabled by set-
ting the jump frequency to 0 Hz.
Jump fre-
Always ensure that the following
quency 2
applies:
d3-02
d3-01 ≥ d3-02 ≥ d3-03
Operation in the jump frequency
Jump Freq 2
range is prohibited but during
acceleration and deceleration, the
speed changes smoothly without
Jump fre-
jumping.
quency 3
d3-03
Jump Freq 3
Jump fre-
Sets the jump frequency band-
quency width
width in Hz.
d3-04
The jump frequency range will be
Jump
Bandwidth
the jump frequency ± d3-04.
Field Weakening: d6
Name
Param-
eter
LCD
Number
Display
Set the Inverter output voltage
Field weaken-
when the field weakening com-
ing level
mand is input.
It is enabled when the field weak-
d6-01
ening command is set for a multi-
function input.
Field-Weak
Set the level as a percentage tak-
Lvl
ing the voltage set in the V/f pat-
tern as 100%.
Set the lower limit in Hz of the
Field fre-
quency
frequency range where field con-
trol is valid.
The field weakening command is
d6-02
valid only at frequencies above
Field-Weak
this setting and only when the
Freq
speed is in agreement with the
current speed reference.
Setting
Description
Range
0.0 to
120.0
0.0 to
20.0
Setting
Description
Range
0 to
100
0.0 to
120.0
Change
RS-422A/
Factory
during
Access
485
Setting
Opera-
Level
Register
tion
0.0 Hz
No
A
294H
0.0 Hz
No
A
295H
0.0 Hz
No
A
296H
1.0 Hz
No
A
297H
Change
RS-422A/
Factory
during
Access
485
Setting
Opera-
Level
Register
tion
80%
No
A
2A0H
0.0 Hz
No
A
2A1H
Parameter Tables
Page
6-24
6-24
6-24
6-24
Page
6-28
6-28
17
5-

Advertisement

Table of Contents