Clearing Cumulative Operation Time
Set the cumulative operation time initial value in time units in parameter o2-07. Set o2-07 to 0 to clear U1-13
(inverter Operating Time).
Clearing Inverter Cooling Fan Operation Time
Set the fan operation time initial value in time units in parameter o2-10. Set o2-10 to 0 to clear U1-40 (Cooling
Fan Operating Time).
Copying Parameters
The Digital Operator can perform the following three functions using the built-in EEPROM (non-volatile
memory).
•
Store Inverter parameter set values in the Digital Operator (READ)
•
Write parameter set values stored in the Digital Operator to the Inverter (COPY)
Compare parameter set values stored in the Digital Operator with Inverter parameters (VERIFY)
•
Related Parameters
Param-
eter
Number
Copy function selection
o3-01
Read permitted selec-
o3-02
-82
6
Name
LCD Display
0: Normal operation
1: READ (Inverter to Operator)
Copy Func Select
2: COPY (Operator to Inverter)
3: Verify (compare)
0: Read prohibited
tion
1: Read permitted
Copy Allowable
Setting
Description
Range
0 to 3
0 or 1
Change
Factory
during
Access
Setting
Opera-
Level
tion
0
No
A
0
No
A