Copying Parameters - Omron I537-E2-01 User Manual

Table of Contents

Advertisement

Clearing Cumulative Operation Time
Set the cumulative operation time initial value in time units in parameter o2-07. Set o2-07 to 0 to clear U1-13
(inverter Operating Time).
Clearing Inverter Cooling Fan Operation Time
Set the fan operation time initial value in time units in parameter o2-10. Set o2-10 to 0 to clear U1-40 (Cooling
Fan Operating Time).

Copying Parameters

The Digital Operator can perform the following three functions using the built-in EEPROM (non-volatile
memory).
Store Inverter parameter set values in the Digital Operator (READ)
Write parameter set values stored in the Digital Operator to the Inverter (COPY)
Compare parameter set values stored in the Digital Operator with Inverter parameters (VERIFY)
Related Parameters
Param-
eter
Number
Copy function selection
o3-01
Read permitted selec-
o3-02
-82
6
Name
LCD Display
0: Normal operation
1: READ (Inverter to Operator)
Copy Func Select
2: COPY (Operator to Inverter)
3: Verify (compare)
0: Read prohibited
tion
1: Read permitted
Copy Allowable
Setting
Description
Range
0 to 3
0 or 1
Change
Factory
during
Access
Setting
Opera-
Level
tion
0
No
A
0
No
A

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents