RS-422A/485 Message Example
An example of RS-422A/485 command/response messages is given below.
Reading Storage Register Contents
Read the contents of the storage register only for specified quantities. The addresses must be consecutive,
starting from a specified address. The data content of the storage register are separated into higher 8 bits and
lower 8 bits.
The following table shows message examples when reading status signals, error details, data link status and
frequency references from the slave 2 Inverter.
Command Message
Slave Address
Function Code
Start
Address
(Register-
number)
Quantity
(10H Max)
CRC-16
-56
6
(During Normal Operation)
02H
Slave Address
03H
Function Code
Number of attached
Higher
00H
data bytes
Lower
20H
Lead stor-
age register
Higher
00H
Lower
04H
Next stor-
age register
Higher
45H
Lower
F0H
Next stor-
age register
Next stor-
age register
CRC-16
Response Message
02H
Slave Address
03H
Function Code
08H
Higher
00H
Lower
65H
Higher
00H
Lower
00H
Higher
00H
Lower
00H
Higher
01H
Lower
F4H
Higher
AFH
Lower
82H
Response Message
(During Error)
02H
83H
Error code
03H
Higher
F1H
CRC-16
Lower
31H