Sourcen:function:mode - HP E1418A User Manual

8/16-channel d/a converter module
Hide thumbs Also See for E1418A:
Table of Contents

Advertisement

SOURce
n
:FUNCtion:MODE
Parameters
Comments
Chapter 3
n
SOURce
:FUNCtion:MODE <
voltage output.
Parameter
Parameter
Name
n
keyword
SOURce
mode
discrete
<
>
In the keyword,
SOURce
1 to 8 for
E1418A, E1418A Option 002
1 to 16 for
E1418A Option 001, E1418A Option 003.
Values of n outside these ranges will generate an error.
Following this command, the output is disabled and set to either 0 A or 0 V.
If the module is in the wait-for-trigger state when this command is received, an
error is generated.
This command is affected by the state of the P/J jumper for this channel on the
terminal module. If the P/J jumper is not set to program selectable this command
will return an error. This jumper is described on page 31.
*RST Condition:
If the P/J jumper is set to program selectable:
output mode is set to voltage, 0 volts output, output relay open.
If the P/J jumper is set to jumper selectable:
output mode is set by the V/I jumper, 0 volts or amps, output relay open.
Related Commands:
commands,
SOURce
n
mode
configures channel n for either current or
>
Type
CURRent or VOLTage
n, the valid range of n is:
n
SOURce
:FUNCtion:MODE?
:VOLTage...
commands
HP E1418A SCPI Command Reference
SOURce
Range of
Values
1 to 8 or 1 to 16
,
n
SOURce
:CURRent...
Default
1
none