If The Chimney Liner Does Not Align With The Insert's Flue Outlet - Enerzone Destination 2.3 Insert Installation And Operation Manual

Table of Contents

Advertisement

B) Your dealer may offer a liner fastening system (AC02006), sold separately. Follow the
installation instructions provided with the liner fastening system.

9.5.2 If the chimney liner does not align with the insert's flue outlet

You can install a liner offset adapter (AC01370), which is sold separately. Please note that
an offset adaptor reduces the free flow of exhaust gases and may result in smoke roll-out
from the insert when it's door is opened for loading. Only use an offset adaptor if a) there is
no other alternative and b) if the total height of the fireplace and chimney is at least 20 feet.
If you must install a liner offset adapter, secure the three brackets with the three screws
provided (30131) on top of the insert in the three holes in front of the flue outlet. The long
end of the brackets must be attached to the insert. The brackets and screws are in the
insert's owner's manual kit. Then follow the instructions in the manual provided with the
liner offset adapter kit.
Destination 2.3 Insert Installation and Operation Manual
41