Minimum Vent Configuration
Use 5x8" Diameter Coaxial Vent
NOTE: Use the included pipe shield and both 8" firestops (use on front and back of wall
penetration).
The termination must fall within the shaded area shown in the chart. Use the indicated
restrictor positions.
One 45° elbow may be used on the horizontal run.
HINT: Use minimum vent kit "H" from Travis Industries (additional vent will be required).
NG (Natural Gas)
12" (305mm) Section
LP (Propane)
12" (305mm) Section
© Travis Industries
Installation
(for qualified installers only)
3 feet (0.915m)
0 feet
3 feet (0.915m)
0 feet
Exhaust Restrictor # 1 (stock)
Diffuser Closed (stock)
Intake Restrictor # 1 (stock)
Min. 24" (600mm) Horizontal Section
Max. 18' (5.5M) Horizontal Section(s)
Exhaust Restrictor # 0 (removed)
Diffuser Closed (stock)
Intake Restrictor # 1 (stock)
Min. 24" (600mm) Horizontal Section
Max. 14' (4.2M) Horizontal Section(s)