Figure 3-5. Scxi-1163 Digital Output Diagram; Table 3-2. Channel And Bank Assignments - National Instruments SCXI-1163 User Manual

32-channel isolated digital output module
Hide thumbs Also See for SCXI-1163:
Table of Contents

Advertisement

Chapter 3
output channels and the Vcc and ground connections. Table 3-2 shows the channel and port
assignments.
These outputs are open-collector outputs with 4.7 k pullups, which can sink 12 mA while
maintaining an output voltage below 0.6 V. The rise time of the outputs is 1 sec into a 100 pF
load; you can obtain shorter rise times by adding additional pullup resistors between the output
and Vcc for that port.
Note: It is important to notice that this module has no access to the analog backplane; this
protects the backplane from faults when high voltages are available at the module
outputs.
Bank
0
1
2
3
4
5
6
7
© National Instruments Corporation
V
CC
4.7 k
V
OUT
GND

Figure 3-5. SCXI-1163 Digital Output Diagram

Table 3-2. Channel and Bank Assignments

Channels
0, 1, 2, 3, Vcc, GND
4, 5, 6, 7, Vcc, GND
8, 9, 10, 11, Vcc, GND
12, 13, 14, 15, Vcc, GND
16, 17, 18, 19, Vcc, GND
20, 21, 22, 23, Vcc, GND
24, 25, 26, 27, Vcc, GND
28, 29, 30, 31, Vcc, GND
TTL Input from
SCXI-1163
Data Register
Front Connector Pins
B30, A30, B29, A29, C30, C29
B26, A26, B25, A25, C26, C25
B22, A22, B21, A21, C22, C21
B18, A18, B17, A17, C18, C17
A13, B13, A14, B14, C13, C14
A9, B9, A10, B10, C9, C10
A5, B5, A6, B6, C5, C6
A1, B1, A2, B2, C1, C2
3-7
Theory of Operation
SCXI-1163 User Manual