Overview: The eFlow6NV power supply/chargers convert a 220VAC (working range 198VAC - 256VAC), 50/60Hz input to a 12VDC or 24VDC nominal output (see Power Supply Configuration Reference Chart and Specifications). eFlow6NV Series Power Supply Configuration Reference Chart: Nominal DC Outputs...
4. Measure output voltage before connecting devices. This helps avoiding potential damage. 5. Connect devices to be powered: a. For eFlow6NV/eFlow6NXV connect devices to terminals marked [- DC +] (Fig. 1h, pg. 3). b. For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 8 marked [1P &...
Stand-by battery connections. Maximum charge current 1.54 amp (non power-limited) (Fig. 1g, pg. 5). Terminal Identification: Power Distribution Module Terminal Legend Terminal Legend Function/Description PD8/PD8CB PD16W/PD16WCB 1P to 8P 1P to 16P Positive DC power outputs. 1N to 8N 1N to 16N Negative DC power outputs. - 4 - eFlow6NV Series...
Page 5
Fig. 1 - eFlow6NV Board configuration 10A 32V 5A 250V 5A 250V BAT FAIL AC FAIL AC DELAY SHUTDOWN 1 min. enable TRIGGER EOL NC C NO NC C NO + AUX – 2 hr. disable SUPERVISED RESET Trouble/Time Limited Warning of Stand-by Batteries: The Time Limited Warning circuit must be connected for local or remote annunciation with an Amber or Red LED to indi- cate DC Trouble (low battery, loss of battery or when 95% of the stand-by battery has been depleted).
9 10 11 12 13 14 15 16 outputs outputs protected protected outputs outputs From From Power Power Supply Supply Board Board (Factory (Factory Installed) Installed) For continuous protection against risk of fire replace fuses with same type and rating. 3.5A 250V - 6 - eFlow6NV Series...
Page 7
Fig. 5 - eFlow6NV configuration Edge of Enclosure Enclosure to Access Control Sentrol Panel or model # 3012 U.L. Listed Tamper Switch Reporting or equivalent Device (Not Included) Door Green Lead Wire Strap (ground) 220VAC (from power mains Enclosure PD8/PD8CB...
Page 8
NEC Power-Limited Wiring Requirements for eFlow6NV Models: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits.
Page 9
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing. 12AH Rechargeable batteries are the largest batteries that can fit in this enclosure. An external battery enclosure must be used if using the 40AH or 65AH batteries. eFlow6NV Series - 9 -...
Appendix A - Compatible Devices A.1 Four (4) Wire Smoke Detectors Table A-1 below lists four (4) wire smoke detectors compatible with eFlow6NV output. System Sensor Max Stand-by Alarm Current Detector Type Smoke Detector/Base Current (mA) (mA) B112LP Base 0.12...
Page 15
Notes: Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 website: www.altronix.com, e-mail: info@altronix.com. Made in U.S.A. MEMBER IIeFlow6NV Series H27O eFlow6NV Series...
Page 16
6 amp 1 amp 910mV eFlow6NXV, eFlow6NX8V, eFlow6NX8DV, eFlow6NX16V, eFlow6NX16DV Overview: The eFlow6NV series power supply/chargers convert a 220VAC, 50/60Hz input, to a 12VDC or 24VDC output. Stand-by Specifications: Fire Applications Access Control Burg. Applications Battery 24 hr. Stand-by/5 min. Alarm Applications Stand-by 4 hr.