Page 1
- Eight (8) Class 2 power-limited PTC protected outputs. - Management interface for eFlow power supply/charger. - Two (2) network controlled Form “C” relays. - Built-in Charger for sealed lead acid or gel type batteries. Installation Guide More than just power. Rev. eFlow104NK8QP-072420...
Page 2
Overview: Altronix eFlow104NK8QP and eFlow104NK8DQP convert a 120VAC 60Hz input into eight (8) fuse protected 12VDC or 24VDC outputs with a total of 10A max. Units include an unswitched aux. output. They also offers a suite of features that includes fire alarm disconnect, over voltage protection, and low power disconnect which prevents deep discharge of stand-by batteries.
Specifications: Inputs: Fire Alarm Disconnect: eFlow104NB: eFlow104NB: • 120VAC, 60Hz, 4.5A. • Supervised Fire Alarm disconnect (latching or LINQ8PD/LINQ8PDCB: non-latching) 10K EOL resistor. Operates on a • 24VDC from eFlow104NB. normally open (NO) or normally closed (NC) trigger. • 12VDC from VR6 voltage regulator. LINQ8PD(CB): •...
13. Installation of tamper switch: Mount UL Listed tamper switch (Altronix model TS112 or equivalent) at the top of the enclosure. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 6a, pg. 8).
Wiring: Use 18 AWG or larger for all low voltage power connections. Note: Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery). Maintenance: Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level eFlow104NB: 24VDC nominal rated @ 10A max.
LED Diagnostics: eFlow104NB Power Supply/Charger Red (DC) Green (AC/AC1) Power Supply Status Normal operating condition. Loss of AC. Stand-by battery is supplying power. No DC output. Loss of AC. Discharged or no stand-by battery. No DC output. LINQ8PD and LINQ8PDCB Networkable Power Distribution Module Flash Codes Description Charge/Discharge current working properly BAT LOCAL...
Page 8
-- OUT8 + AC FAIL NC C NC C BAT FAIL DC Output to devices (eFlow104NK8QP - non power-limited, eFlow104NK8QPD - power-limited) Optional Rechargeable Stand-by Battery Optional Rechargeable Stand-by Battery for UL294 Applications for UL294 Applications Note: 12V batteries required for Note: 12V batteries required for ULC-S319 installations.
Page 9
Network Setup: –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– Please be sure to visit altronix.com for latest firmware and installation instructions. –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– Altronix Dashboard USB Connection: The USB connection on the LINQ8PD(CB) is used for Network. When connected to a PC via the USB cable the LINQ8PD(CB) will receive power from the USB port allowing programming of the LINQ8PD(CB) prior to being connected to the power supply.
Browser Setup: When not using the Altronix Dashboard USB connection for the initial Network setup the LINQ8PD(CB) needs to be connected to any DC power supply(ies) or eFlow power supply(ies) being monitored prior to programing. Factory Default settings • IP Address: 192.168.168.168...
Page 12
(38.1mm) (38.1mm) Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056 website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty | Made in U.S.A. IIeFlow104NKA8(D) G24T MEMBER - 12 -...