Troubleshooting Outdoor Components
Reactor
Reactor Resistance Check:
The line reactor helps to smooth the inrush current , reduce harmonics and noise, and buffers the system, pro-
tecting the electronics from transient voltage noise. The resistance between the coils will be very low, approxi-
mately .3 ohms and should not have any resistance to ground. You should disconnect the wires from the reactor
before taking any readings.