UPS OPERATING INSTRUCTIONS
t
7-28
Power Xpert
9395 Plus 1 UPS (225–275 kVA) Installation and Operation Manual
7.3.24

Using the UPS LOAD OFF Pushbutton or Command

A UPS Load Off is initiated by the
Load Off command on the UPS Control Command screen, or the Load Off command
on the Bypass Control Command screen. The UPS
by powering down the UPS and de‐energizing the critical load.
The UPS (including Bypass) remains off until restarted.
To use the
LOAD OFF
1.
Press the
LOAD OFF
The Load Off screen is displayed, providing a choice to proceed or abort the
shutdown.
All power to the critical load is lost when the LOAD OFF is selected in the following step. You should use this
feature only when you want to de‐energize the critical load.
2.
To shut down the UPS, press
three seconds. To abort the shutdown, press
When LOAD OFF is selected and held for three seconds, the input, output,
battery, and bypass backfeed contactors open, and the power module is turned
off.
Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and
cleared.
3.
To restart the UPS after pressing the
in paragraph 7.3.1 or 7.3.8.
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.
To use the
LOAD OFF
1.
Press the
CONTROLS
screen is displayed.
2.
On the System Status screen, select either the
3.
Press the
CONTROLS
Bypass Control Command screen is displayed.
4.
On the Control Command screen, select
5.
Press the
SELECT
The Load Off screen is displayed, providing a choice to proceed or abort the
shutdown.
pushbutton from the main menu bar, the
LOAD OFF
pushbutton:
pushbutton.
C A U T I O N
from the Load Off menu bar, and hold for
LOAD OFF
C A U T I O N
LOAD OFF
W A R N I N G
command:
pushbutton on the main menu bar. The System Status
pushbutton on the System Status menu bar. The UPS or
LOAD OFF
pushbutton on the Command menu bar.
S
164201710 Rev 7
controls the UPS output
LOAD OFF
.
CANCEL
pushbutton, follow the procedure
or the
command.
UPS
BYPASS
.
www.eaton.com/powerquality