5.9 Heat cut-out

MENU > Settings > Heat cut-out
The setting "Summer cut-out" under "Optimization" for the heating
circuit in question determines a heating cut-out when the outdoor
temperature exceeds the set value.
A filtering constant for calculating the accumulated outdoor
temperature is internally set to a value of "250". This filtering
constant represents an average building with solid outer and inner
walls (bricks).
An option for differentiated cut-out temperatures, based on a
set summer period, can be utilized in order to avoid discomfort
at falling outdoor temperature. Furthermore, separate filtering
constants can be set.
The factory set values for Summer period start and Winter period
start are set to same date: May, 20 (Date = 20, Month = 5).
This means:
"Differentiated cut-out temperatures" are disabled (not active)
Separate "Filtering constant" values are disabled (not active)
In order to enable differentiated
cut-out temperature based on summer / winter period
filtering constants
the start dates for the periods must be different.