Installation Guide
MENU > Settings > Control par.
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
Motor pr. (motor protection)
Circuit
All
Prevents the controller from unstable temperature control (and resulting
actuator oscillations). This can occur at very low load. The motor protection
increases the lifetime of all involved components.
* See Appendix "Parameter ID overview"
OFF:
Motor protection is not activated.
Value:
Motor protection is activated after the set activation
delay in minutes.
MENU > Settings > Boiler
MENU > Settings > Control par.
MENU > Settings > Control par., cool.
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
MENU > Settings > Control par. 3
MENU > Settings > Control par., P circ.
MENU > Settings > Control par., P refill
Xp (proportional band)
Circuit
All
* See Appendix "Parameter ID overview"
Set the proportional band. A higher value will result in a stable but
slow control of the flow / duct temperature.
MENU > Settings > Boiler
MENU > Settings > Control par.
MENU > Settings > Control par., cool.
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
MENU > Settings > Control par. 3
MENU > Settings > Control par., P circ.
MENU > Settings > Control par., P refill
Tn (integration time constant)
Circuit
All
* See Appendix "Parameter ID overview"
Set a high integration time constant (in seconds) to obtain a slow
but stable reaction to deviations.
A low integration time constant will make the controller react fast
but with less stability.
70
DEN-SMT/DK
ECL Comfort 210 / 310, application A260
1x174
Setting range
Factory setting
*
1x184
Setting range
Factory setting
*
1x185
Setting range
Factory setting
*
Recommended for duct systems with variable load.
*
*
*
VI.LG.F2.02
Danfoss District Energy