MENU > Settings > Application
P demand
Circuit
All
The circulation pump in the master circuit can be controlled in relation to
the master circuit's demand or slave circuit's demand.
* See Appendix "Parameter ID overview"
Heating applications:
OFF:
The circulation pump is ON when the desired flow
temperature in the heating circuit is higher than the
value set in 'P heat T'.
ON:
The circulation pump is ON when the desired flow
temperature from slaves is higher than the value set in
'P heat T'.
Cooling applications:
OFF:
The circulation pump is ON when the desired flow
temperature in the cooling circuit is lower than the value
set in 'P cool T'.
ON:
The circulation pump is ON when the desired flow
temperature from slaves is lower than the value set in
'P cool T'.
MENU > Settings > Application
DHW priority (closed valve / normal operation)
Circuit
All
The heating circuit can be closed when the controller acts as slave and when
DHW heating / charging is active in the master.
* See Appendix "Parameter ID overview"
OFF:
The flow temperature control remains unchanged
during active DHW heating / charging in the master
controller.
ON:
The valve in the heating circuit is closed* during active
DHW heating / charging in the master controller.
* The desired flow temperature is set to the value set in
'Frost pr. T'
Danfoss District Energy
ECL Comfort 210 / 310, application A260
1x050
Setting range
Factory setting
*
1x052
Setting range
Factory setting
*
The circulation pump is always controlled according to frost protection
conditions.
*
This setting must be considered if this controller is a slave.
*
VI.LG.F2.02