MENU > Settings > Flow / power limit
Low limit Y1 (flow / power limitation, low limit, Y-axis)
Circuit
All
Set the flow / power limitation referring to the outdoor temperature set in
'High T out X1'.
* See Appendix "Parameter ID overview"
The corresponding X coordinate is set in 'High T out X1'.
MENU > Settings > Flow / power limit
Low T out X2 (flow / power limitation, low limit, X-axis)
Circuit
All
Set the outdoor temperature value for the high flow / power limitation.
* See Appendix "Parameter ID overview"
The corresponding Y coordinate is set in 'High limit Y2'.
MENU > Settings > Flow / power limit
High T out X1 (flow / power limitation, high limit, X-axis)
Circuit
All
Set the outdoor temperature value for the low flow / power limitation.
* See Appendix "Parameter ID overview"
The corresponding Y coordinate is set in 'Low limit Y1'.
Danfoss District Energy
ECL Comfort 210 / 310, application A260
1x117
Factory setting
Setting range
*
1x118
Setting range
Factory setting
*
1x119
Factory setting
Setting range
*
The limitation function can overrule the set 'Temp. min' of the desired
flow temperature.
*
*
*