Danfoss ECL Comfort 210 Installation Manual page 66

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
MENU > Settings > Application
MENU > Settings > Optimization
Total stop
Circuit
All
Decide whether you want a total stop during the saving temperature period.
* See Appendix "Parameter ID overview"
OFF:
No total stop. The desired flow temperature is reduced
according to:
• desired room temperature in saving mode
• auto saving
ON:
The desired flow temperature is lowered to the set value
in 'Frost pr. ' The circulation pump is stopped but frost
protection is still active, see 'P frost T'.
MENU > Settings > Optimization
Pre-stop (optimized stop time)
Circuit
All
Disable the optimized stop time.
* See Appendix "Parameter ID overview"
OFF:
The optimized stop time is disabled.
ON:
The optimized stop time is enabled.
66
DEN-SMT/DK
ECL Comfort 210 / 310, application A260
1x021
Setting range
Factory setting
*
1x026
Setting range
Factory setting
*
Desired flow temp. °C
*
Desired flow temp. °C
The min. flow temperature limitation ('Temp. min.') is overruled when
'Total stop' is ON.
Example: Optimization of Comfort from 07:00 - 22:00
07:00
*
Optimization start
VI.LG.F2.02
Total stop = ON
'Frost pr.'
Time
Total stop = OFF
'Frost pr.'
Time
22:00
Schedule
Pre-stop OFF
Pre-stop ON
Optimization stop