Danfoss ECL Comfort 210 Installation Manual page 85

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
Alarm overview, list:
Alarm
Description:
no.:
2
Temp. monitor, circuit 1
3
Temp. monitor, circuit 2
32
T sensor defect
To find the reason for an alarm:
select MENU
select 'Alarm'
select 'Alarm overview' . A "bell" will be shown at the alarm in
question.
Alarm overview (example):
2: Max. temp.
3: Temp. monitor
32: T sensor defect
The numbers in the 'Alarm overview' refer to the alarm number
in the Modbus communication.
To reset an alarm:
When the "bell" is present to the right of the alarm line, place the
cursor at the alarm line in question and press the dial.
To reset alarm 32:
MENU > Common controller settings > System > Raw input
overview: The sensor in question is marked and the alarm can be
reset.
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Alarm > Charge T
MENU > Alarm > Temp. monitor
Upper difference
Circuit
All
The alarm is activated if the actual flow / duct temperature increases more
than the set difference (acceptable temperature difference above the desired
flow / duct temperature). See also 'Delay'.
* See Appendix "Parameter ID overview"
OFF:
The related alarm function is not active.
Value:
The alarm function is active if the actual temperature
gets above the acceptable difference.
Danfoss District Energy
ECL Comfort 210 / 310, application A260
Alarm
Sensor
type:
ref.:
1
S3
1
S4
2
all
1x147
Factory setting
Setting range
*
Flow / duct temp. °C
*
VI.LG.F2.02
Upper difference (set
value)
Desired flow / duct
temp.
Time
DEN-SMT/DK
85

Advertisement