Danfoss ECL Comfort 210 Installation Manual page 98

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
MENU > Common controller > System > M-bus config.
Command
Circuit
-
NONE / INIT / SCAN / GATEW
The ECL Comfort 310 is M-bus master. In order to verify connected energy
meters, different commands can be activated.
NONE:
No command activated
INIT:
Initialization is activated
SCAN:
Scanning is activated in order to search for connected
energy meters. The ECL Comfort 310 detects the
M-bus addresses of up to 5 connected energy meters
and place these automatically in the "Energy meters"
section. The verified address is placed after "Energy
meter 1 (2, 3, 4, 5)"
GATEW: The ECL Comfort 310 acts as a gateway between
energy meters and ECL Portal. Used only for service.
MENU > Common controller > System > M-bus config.
M-bus address
Energy meter 1 (2, 3, 4, 5)
Circuit
-
The set or verified address of energy meter 1 (2, 3, 4, 5).
0:
Normally not used
1 - 250:
Valid M-bus addresses
251 - 254: Special functions. Use only M-bus address 254 when
one energy meter is connected.
255:
Not used
MENU > Common controller > System > M-bus config.
Type
Energy meter 1 (2, 3, 4, 5)
Circuit
-
Selecting data range from the M-bus telegram.
0:
Small data set, small units
1:
Small data set, large units
2:
Large data set, small units
3:
Large data set, large units
4:
Volume and energy data only
(example: HydroPort Pulse)
98
DEN-SMT/DK
ECL Comfort 210 / 310, application A260
5998
Setting range
Factory setting
NONE
6000
Setting range
Factory setting
0 - 255
255
6001
Setting range
Factory setting
0 - 4
Scan time can take up to 12 minutes.
When all energy meters are found, the command can be changed
to INIT or NONE.
Data examples:
0:
0
Flow temp., return temp., flow, power, acc. volume, acc. energy.
3:
Flow temp., return temp., flow, power, acc. volume, acc. energy,
tariff 1, tariff 2.
See also the "Instructions, ECL Comfort 210 / 310, communication
description" for further details.
See also Appendix for detailed description of "Type".
VI.LG.F2.02
Danfoss District Energy