Danfoss ECL Comfort 210 Installation Manual page 53

Hide thumbs Also See for ECL Comfort 210:
Table of Contents

Advertisement

Installation Guide
Example, minimum return temperature limitation;
return temperature gets lower than limit
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Return limit
Con.T, re. T lim. (Constant temperature mode, return
temperature limitation)
Circuit
All
The "Con. T, ret. T limit" is the return temperature limitation value when the
circuit is set to override mode type "Const. T" (= Constant temperature).
* See Appendix "Parameter ID overview"
Value: Set the return temperature limitation
Danfoss District Energy
ECL Comfort 210 / 310, application A260
1x028
Setting range
Factory setting
*
= Temperature
T
= Temperature
Y
= Time
X
# 1 # = Return temperature
# 2 # = Return temperature limit
# 3 # = Desired flow temperature
# 4 # = Action point
*
Override mode
When ECL Comfort is in Scheduled mode, a contact (switch) signal can
be applied to an input in order to override to Comfort, Saving, Frost
Protection or Constant temperature. As long as the contact (switch)
signal is applied, the override is active.
VI.LG.F2.02
DEN-SMT/DK
53

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl comfort 310

Table of Contents