Installation Guide
MENU > Settings > Return limit
DHW, ret. T limit
Circuit
All
When an addressed slave is active in DHW-tank heating / charging, the
return temperature limitation in the master can be set.
Notes:
The master circuit must be set to react on the desired flow temperature
in the slave(s). See "Demand offset" (ID 11017).
The slave(s) must be set to send its / their desired flow temperature to the
master. See "Send desired T" (ID 1x500).
* See Appendix "Parameter ID overview"
OFF:
No influence from slaves. The return temperature
limitation is related to settings in "Return limit".
Value: Return temperature limitation value when slave is in
DHW tank heating / charging operation.
MENU > Settings > Return limit
High T out X1 (return temp. limitation, high limit, X-axis)
Circuit
All
Set the outdoor temperature value for the low return temperature limitation.
* See Appendix "Parameter ID overview"
The corresponding Y coordinate is set in 'Low limit Y1'.
MENU > Settings > Return limit
Low limit Y1 (return temp. limitation, low limit, Y-axis)
Circuit
All
Set the return temperature limitation referring to the outdoor temperature
value set in 'High T out X1'.
* See Appendix "Parameter ID overview"
The corresponding X coordinate is set in 'High T out X1'.
MENU > Settings > Return limit
Low T out X2 (return temp. limitation, low limit, X-axis)
Circuit
All
Set the outdoor temperature value for the high return temperature
limitation.
* See Appendix "Parameter ID overview"
The corresponding Y coordinate is set in 'High limit Y2'.
54
DEN-SMT/DK
ECL Comfort 210 / 310, application A260
1x029
Setting range
Factory setting
*
1x031
Setting range
Factory setting
*
1x032
Setting range
Factory setting
*
1x033
Setting range
Factory setting
*
*
# 1 # = Master, example A266, address 15
# 2 # = Slave, example A237, address 9
# 3 # = Slave, example A367, address 6
Some examples of applications with DHW-tank heating / charging are:
A217, A237, A247, A367, A377
*
*
*
VI.LG.F2.02