Heating cut-out -
line 1
1
1
Limit for heating cut-out
Circuit
I / (II)
Set the outdoor temperature limit at which you
want the heating system to stop.
The valve closes and after about 3 min. the heating
circulation pump stops.
The min. limitation set in line 2 will be ignored.
Temp.
Actual
outdoor temp.
18 °C
Heating
This function can save energy by stopping the heating system
when the outdoor temperature gets above a set limit. The heating
system switches ON again when the outdoor temperature and
the accumulated outdoor temperature become lower than the set
limit.
The heating cut-out is only active when the controller mode is
scheduled operation. When the limit value is set to 30, there is no
heating cut-out.
The grey
side of the
ECL Card
1
1
2
2
ON
ON
1
8
Setting range
10 ... 30 °C
Heating OFF
Factory setting
20 / (20) °C
Accumulated
outdoor temp.
Heating
Time