Installation Guide
MENU > Settings > Flow temperature
MENU > Settings > Inlet temperature
Temp. min. (duct / flow / inlet temp. limit, min.)
Circuit
All
* See Appendix "Parameter ID overview"
Set the min. duct / flow / inlet temperature for the system. The
desired duct / flow / inlet temperature will not be lower than this
setting. Adjust the factory setting, if required.
MENU > Settings > Flow temperature
MENU > Settings > Inlet temperature
Temp. max. (duct / flow / inlet temp. limit, max.)
Circuit
All
* See Appendix "Parameter ID overview"
Set the max. flow / duct / inlet temperature for the system. The
desired temperature will not be higher than this setting. Adjust
the factory setting, if required.
48
DEN-SMT/DK
ECL Comfort 210 / 310, application A260
1x177
Setting range
Factory setting
*
1x178
Factory setting
Setting range
*
'Temp. min. ' is overruled if 'Total stop' is active in Saving mode or
'Cut-out' is active.
'Temp. min. ' can be overruled by the influence from the return
temperature limitation (see 'Priority').
*
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .
The setting of 'heat curve' is possible for heating circuits only.
*
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .
VI.LG.F2.02
Danfoss District Energy