Installation Guide
MENU > Settings > Duct T limit
MENU > Settings > Room limit
Infl. - min. (room / duct temp. limitation, min.)
Circuit
All
Determines how much the desired flow / duct temperature will be influenced
(increased) if the actual room / duct temperature is lower than the desired
room / duct temperature (P control).
* See Appendix "Parameter ID overview"
9.9:
Maximum influence
5.0:
Medium influence
2.0:
Minor influence
0.0:
No influence
Danfoss District Energy
ECL Comfort 210 / 310, application A260
1x183
Setting range
Factory setting
*
Example 1 (application with heat curve value):
The actual room temperature is 2 degrees too low.
The 'Infl. - min. ' is set to 4.0.
The heat curve slope is 1.8 (see 'Heat curve' in 'Flow temperature').
Result:
The desired flow temperature is changed by (2 x 4.0 x 1.8)
*
14.4 degrees.
Example 2 (application, no heat curve value):
The actual room temperature is 3 degrees too low.
The 'Infl. - min. ' is set to 4.0.
Result:
The desired flow temperature is changed by (3 x 4.0)
12 degrees.
VI.LG.F2.02
DEN-SMT/DK
51