MENU > Settings > Boiler
MENU > Settings > Control par.
MENU > Settings > Control par., cool.
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
M run (running time of the motorized control valve)
Circuit
All
'M run' is the time in seconds it takes the controlled component to move
from fully closed to fully open position.
* See Appendix "Parameter ID overview"
Set the 'M run' according to the examples or measure the running
time by means of a stop watch.
MENU > Settings > Boiler
MENU > Settings > Control par.
MENU > Settings > Control par., cool.
MENU > Settings > Control par., fan
MENU > Settings > Control par., inlet
MENU > Settings > Control par., outlet
MENU > Settings > Control par., P circ.
MENU > Settings > Control par., P refill
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
MENU > Settings > Control par. 3
Nz (neutral zone)
Circuit
All
When the actual flow / duct temperature is within the neutral zone, the
controller does not activate the motorized control valve.
* See Appendix "Parameter ID overview"
Set the acceptable flow /duct temperature deviation.
Set the neutral zone to a high value if you can accept a high
variation in flow temperature.
MENU > Settings > Boiler
MENU > Settings > Control par.
MENU > Settings > Control par., cool.
MENU > Settings > Control par. 1
MENU > Settings > Control par. 2
Min. act. time (min. activation time gear motor)
Circuit
All
The min. pulse period of 20 ms (milliseconds ) for activation of the gear
motor.
* See Appendix "Parameter ID overview"
Danfoss District Energy
ECL Comfort 210 / 310, application A260
1x186
Setting range
Factory setting
*
1x187
Setting range
Factory setting
*
1x189
Setting range
Factory setting
*
How to calculate the running time of a motorized control valve
The running time of the motorized control valve is calculated using
the following methods:
Seated valves
Running time = Valve stroke (mm) x actuator speed (sec. / mm)
Example:
5.0 mm x 15 sec. / mm = 75 sec.
Rotating valves
*
Running time = Turning degrees x actuator speed (sec. / degr.)
Example:
90 degr. x 2 sec. / degr. = 180 sec.
The neutral zone is symmetrical around the desired flow / duct
temperature value, i.e. half the value is above and half the value is
below this temperature.
*
Setting example
2
10
50
*
The setting should be kept as high as acceptable to increase the
lifetime of the actuator (gear motor).
VI.LG.F2.02
Value x 20 ms
40 ms
200 ms
1000 ms
DEN-SMT/DK
71