VERTICAL TERMINATIONS
MIN. / MAX. VERTICAL VENTING (5" x 8")
Figure 22a
Horizontal Vent Heat Shield is not used on vertical venting configurations.
NOTE
Depending on your particular venting needs, a Decreaser may be necessary to terminate venting system.
CAUTION
This gas appliance must not be connected to or joined with any other chimney flue serving another appliance.

RESTRICTOR INSTALLATION

RECOMMENDED:
Vertical terminations over 6ft. (1.82m): 1 restrictor
Maximum vertical terminations: 2 offset restrictors
Large Restrictor
Remove tab (s) to
create small restrictor
Figure 22c
Page 49 has information on restrictor recommendations depending on burner flame appearance and instructions on installation
NOTE
after venting is completed.
VENTING
TERMINATION CAP
MINIMUM: 4ft. (1.22m)
MAXIMUM: 40ft. (12.19m)
Bend tabs to approx. 80 degree
angles to create tension to hold
itself in place when installed.
MIN. / MAX. VERTICAL VENTING
(8" x 6-5/8" DECREASER)
Figure 22b
Slide restrictor into exhaust pipe on top of fireplace with tabs
pointing towards you prior to attaching venting.
22
TERMINATION CAP
MINIMUM: 4ft. (1.22m)
MAXIMUM: 40ft. (12.19m)
8" x 6-5/8" DECREASER
6" (152mm)