VERTICAL TERMINATIONS
CAUTION: This gas appliance must not be connected to or joined with any other chimney flue serving another appliance.
Minimum: 2 ft."(610 mm)
Maximum: 30ft. (9.14m)
Figure 22a

RESTRICTOR INSTALLATION

TO BE USED AT INSTALLER DISCRETION.
Large Restrictor
Remove tab (s) to
create small restrictor
Figure 22b
NOTE: Page 50 has information on restrictor recommendations depending on burner flame appearance and instructions on installation
after venting is completed.
VENTING
Termination Cap
45° Elbow
Bend tabs to approx. 80 degree
angles to create tension to hold
itself in place when installed.
PAGE 22
Slide restrictor into exhaust pipe on top of fireplace with
tabs pointing towards you prior to attaching venting.