2. Modified coefficient table of ambient condition power
The conditions of generator rated output:
Altitude: 0 m
Ambient temperature: 25
Ambient modified coefficient: C (Relative humidity 30%)
Ambient temperature ( )
Altitude
(m)
25
30
0
1
0.98
500
0.93
0.91
1000
0.87
0.85
2000
0.75
0.73
3000
0.64
0.62
4000
0.54
0.52
Note: When the relative humidity is 60%, the modified coefficient is C-0.01
When the relative humidity is 80%, the modified coefficient is C-0.02
When the relative humidity is 90%, the modified coefficient is C-0.03
When the relative humidity is 100%, the modified coefficient is C-0.04
Counting example:
When the rated power of generator is P =5KW, altitude is 1000m, ambient
temperature is 35
, relative humidity is 80%, the rated power of generator is:
P=P
(C-0.02) = 5
(0.82-0.02) = 4KW
N
Relative humidity: 30%
35
40
45
0.96
0.93
0.90
0.89
0.87
0.84
0.82
0.80
0.78
0.71
0.69
0.66
0.6
0.58
0.56
0.5
0.48
0.46
N
-28-

1. SAFETY INSTRUCTIONS

WARNING
Operate carefully and make sure users and others safety.
WARNING
Our generators are designed to give safe and depe-
ndable service if operated according to instructions.
Read and understand the Owner's Manual before
operating the generator. Failure to do so could result in
personal injury or equipment damage.
WARNING
Exhaust gas contains poisonous carbon monoxide.
Never run the generator in an enclosed area.
Be sure to provide adequate ventilation.
WARNING
The muffler becomes very hot during operation and
remains hot for a while after stopping the engine.
Be careful not to touch the muffler while it is hot.
Let the engine cool before
indoors. The engine exhaust system will be heated
during op-eration and remain hot immediately after
stopping the engine. To
attention
to
generator.
storing the generator
prevent
scalding,
pay
the
warning marks attached
to the
-1-

Hide quick links:

Advertisement

loading