ESIE09-08
3.53 "U2 " Power Supply Insufficient or Instantaneous Failure
U2
Remote Control
Display
Applicable
ER*Q 011~016*
Models
Method of
Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction
Detection
Malfunction
When the abnormal voltage of main circuit capacitor built in the inverter and abnormal power
Decision
supply voltage are detected.
Conditions
Supposed
Causes
Troubleshooting
Power supply insufficient
Instantaneous power failure
Defect of outdoor inverter PC board (A2P)
Troubleshooting by Indication on the Remote Controller
193