Daikin ERSQ 011AAV1 Service Manual page 96

Table of Contents

Advertisement

Field Setting
First
Second
code
code
Setting name
7
Option setup
00
Optional bottom plate heater installed
01
Not applicable. Do not change the default
value.
02
Multiple set point pattern
03
Multiple set point 1
04
Multiple set point 2
8
Option setup
00
Remote controller temperature control
01
Status: automatic restart function
02
Emergency mode
03
Status: low noise level
04
Status: freeze up prevention
9
Automatic temperature compensation
00
Leaving water temperature compensation
value
01
Domestic hot water tank compensation
value
02
Thermo ON/OFF admission
A
Option setup
00
Not applicable. Do not change the default
value.
01
Not applicable. Do not change the default
value.
02
Set point: required temperature difference
for leaving and returning water
03
Set point: multiple set point 1 required
temperature value
04
Set point: multiple set point 2 required
temperature value
B
Domestic hot water set points
00
Set point: reheat minimum temperature
01
Set point: reheat maximum temperature
02
Status: weather dependent domestic water
heating
03
Set point: storage temperature
84
Installer setting at variance with
default value
Date
Value
Date
Value
ESIE09-08
Default
value
Range
Step
0
0/1
(OFF)
0
0/1
(OFF)
0 (A)
0/1
0
0/1
(OFF)
0
0/1
(OFF)
1 (ON)
0/1
1 (ON)
0/1
0
0/1
(OFF)
1
1~3
1
0
0~2
1
0
–5~5
0.5
0
–5~5
0.5
0
–5~5
0.5
0
0~2
1
0
0~2
1
10
5~15
1
35
25~80
1
65
25~80
1
35
35~65
1
45
35~75
1
1 (ON)
0/1
70
45~75
1
Test Operation
Unit
°C
°C
°C
°C
°C
°C
°C
°C
°C