SiBE34-802
U2
3.42 "
"
Power Supply Insufficient or Instantaneous Failure
U2
Remote
Controller
Display
Applicable
RXYSQ4~6PA
Models
Method of
Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction
Detection
Malfunction
When the abnormal voltage of main circuit capacitor built in the inverter and abnormal power
supply voltage are detected.
Decision
Conditions
Supposed
Causes
Troubleshooting
Power supply insufficient
Instantaneous power failure
Defect of outdoor unit fan motor
Defect of outdoor inverter PC board (A2P)
Troubleshooting by Indication on the Remote Controller
191