Defrosting Operation - Daikin ERSQ 011AAV1 Service Manual

Table of Contents

Advertisement

ESIE09-08

3.2 Defrosting Operation

The defrost operation is performed to solve frost on the outdoor unit heat exchanger when
heating mode is active to recover the heating capacity.
[Conditions to start]
The defrost operation is started referring following conditions.
*T
[Fan defrosting]
Function
Outdoor heat exchanger heat transfer co-efficient
Temperature of heat-exchange (Tb) < T
Timer (25 min. the minimum)
In addition, outdoor heat-exchanger co-efficient is derived from Tc, Te, and the compressor
load.
can vary but is at least -10°C
def
When compressor stops, 80 sec. at low RPM
At start up compressor, 30 sec. at 950 RPM (step 9)
Then goes back to normal RPM
*
def
Special Control
53