Troubleshooting - Daikin ERSQ 011AAV1 Service Manual

Table of Contents

Advertisement

Troubleshooting by Remote Control
Malfunction code indication by outdoor unit PC board
<Monitor mode>
To enter the monitor mode, push the
MODE (BS1) button when in
"Setting mode 1".
<Selection of setting item>
Push the SET (BS2) button and set
the LED display to a setting item.
<Confirmation of malfunction 1>
Push the RETURN (BS3) button
once to display "First digit" of
malfunction code.
<Confirmation of malfunction 2>
Push the SET (BS2) button once to
display "Second digit" of malfunction
code.
<Confirmation of malfunction 3>
Push the SET (BS2) button once to
display "malfunction location".
<Confirmation of malfunction 4>
Push the SET (BS2) button once to
display "master or slave 1 or slave 2"
and "malfunction location".
Push the RETURN (BS3) button and
switches to the initial status of
"Monitor mode".
∗ Push the MODE (BS1) button and
returns to "Setting mode 1".
126
In-phase malfunction of DIII Net
Abnormal discharge pressure
Abnormal suction pressure
Compressor lock
Over load, over current,
abnormal lock of outdoor unit fan motor
Malfunction of electronic expansion
valve
Faulty sensor of outdoor air
temperature
Abnormal discharge pipe temperature
Abnormal heat exchanger temperature Refrigerant over charge
Faulty sensor of discharge pipe
temperature
Faulty sensor of suction pipe
temperature
Faulty sensor of heat exchanger
temperature
Malfunction of the liquid pipe
temperature sensor
Faulty sensor of subcool heat
exchanger temperature
Faulty sensor of discharge pressure
Faulty sensor of suction pressure
Faulty Inverter PC board
Detail
description
on next
page.
Inverter radiation fin temperature rising Over heating of inverter radiation fin temperature
DC output over current
Electronic thermal
Stall prevention (Limit time)
Transmission error between inverter
and outdoor unit
Contents of malfunction
Detection of DIII Net
HPS activated
Abnormal Pe
Detection of INV compressor lock
Detection of DC fan 1 motor lock
Detection of DC fan 2 motor lock
EV1
EV3
Faulty Ta sensor (short)
Abnormal Td
Faulty Tdi sensor (short)
Faulty Ts1 sensor (short)
Faulty Ts2 sensor (short)
Faulty Tb sensor (short)
Faulty TI sensor (short)
Faulty Tsh sensor (short)
Faulty Pc sensor (short)
Faulty Pe sensor (short)
Faulty IPM
Abnormal Current sensor offset
Abnormal IGBT
Faulty Current sensor
Abnormal SP-PAM over-voltage
Inverter instantaneous over current
Electronic thermal switch 1
Electronic thermal switch 2
Out-of-step
Speed down after startup
Lightening detection
Stall prevention (Current increasing)
Stall prevention (Faulty start up)
Abnormal wave form in startup
Out-of-step
Inverter transmission error
ESIE09-08
Malfunction
code
E1
E3
E4
E5
E7
E9
H9
F3
F6
J3
J5
J6
J7
J9
JA
JC
L1
L4
L5
L8
L9
LC

Troubleshooting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents