Field Setting
[A] Option setup
First
code
A
Notes :
1. When temperature reducing devices are installed, the system can be configured to use multi
2. The selected values for multiple set point should be lower than the value from remote
3. Daikin does not offer any temperature reducing device (TRD). This system (multi set point
98
Second
code
Setting name
Option setup
02
Set point: required temperature difference for
leaving and returning water
03
Set point: multiple set point 1 required
temperature value
04
Set point: multiple set point 2 required
temperature value
[A-02] Temperature difference for leaving and returning water
The unit is designed to support radiator operation. The advised leaving water temperature
(set by the remote controller) for radiators is 65°C. In such a case the unit will be controlled
to realize a temperature difference (ΔT) of 10°C, which means that the returning water to the
unit is around 55°C.
Depending on the installed application (radiators, fan coil units, ...) or situation, it can be
required to change the ΔT. This can be done by changing field setting [A-02].
[A-03] Multi set point 1 temperature.
[A-04] Multi set point 2 temperature.
set points, also the demand PCB (option) is needed.
controller (reference temperature) or domestic hot water temperature (pattern A).
control) only provides the possibility to use multi set point. It's than also the installers
responsibility to make sure that the whole system is operating well.
Default
value
Range
Step
10
5~15
1
35
25~80
1
65
25~80
1
Test Operation
ESIE09-08
Unit
°C
°C
°C