ESIE09-08
[B] Domestic hot water set points
First
code
B
The reheat mode will prevent the domestic hot water from cooling down lower than a certain
temperature. When enabled the indoor unit will deliver hot water to the domestic hot water tank
if the reheat minimum value is reached. The domestic water heating will continue until the
reheat maximum temperature is reached. In this way always a minimum of domestic hot water
is available.
T
D
E
F
G
Field settings
Notes :
1. Remark that the w icon will only be blinking during effective automatic storage operation.
2. During operation it is always possible to cancel the operation by pushing the w button once.
3. Pushing the y button has no influence on the domestic water heating. Domestic hot water
Test Operation
Second
code
Setting name
Domestic hot water set points
00
Set point: reheat minimum temperature
01
Set point: reheat maximum temperature
02
Status: weather dependent domestic water
heating
03
Set point: storage temperature
[b-00] Set point: reheat minimum temperature (see figure below).
[b-01] Set point: reheat maximum temperature (see figure below).
A
B
A
Storage operation (if activated)
B
Reheat operation (if activated)
C
Disinfection operation (if activated)
D
Disinfection operation temperature [5-00] (e.g. 70°C)
E
Hot water storage temperature [b-03] (e.g. 60°C)
F
Reheat maximum water temperature [b-01] (e.g. 45°C)
G
Reheat minimum water temperature [b-00] (e.g. 35°C)
t
Time
T
Domestic hot water tank temperature
Presence of the permanently lit w icon does not mean that automatic storage is enabled,
but only means that reheat is enabled.
heating is only switched on or off by means of the w button and/or disabling the storage
schedule timer.
C
t
Field Setting
Default
value
Range
Step
35
35~65
1
45
35~75
1
1 (ON)
0/1
70
45~75
1
Unit
°C
°C
°C