ESIE09-08
[7] Option setup
First
code
7
Test Operation
Second
code
Setting name
Option setup
00
Optional bottom plate heater installed
02
Multiple set point pattern
03
Multiple set point 1
04
Multiple set point 2
[7-00] Bottom plate heater option
An optional bottom plate heater can be installed in your outdoor unit. In case an ERRQ*
outdoor unit (special model with freeze-up countermeasures) is installed, the unit will have
the bottom plate heater already standard installed.
If the bottom plate heater is installed, its operation must be enabled by field setting. Default
[7-00] = 0 which means no bottom plate heater is installed. Set [7-00] to 1 if the bottom plate
heater is installed.
[7-02] Select multiple set point pattern A or B
Multi set point control according pattern A
During normal operation, domestic water heating and space heating modes are
separated and activated intermittent to fulfil a simultaneous request. Therefor multiple set
point pattern A can be configured to allow simultaneous domestic water and space
heating without intermission.
Multi set point control according pattern B
The basic setup of multiple set point pattern B is the same as a normal classic design, so
AGAIN no domestic water heating and space heating is possible simultaneously. Multiple
set point pattern B is focussed on space heating operation and allows using multiple
water set points in combination with the remote controller or external room thermostat.
The configuration of pattern B allows space heating set points and the domestic hot
water set point.
[7-03] Activation for multiple set point 1
[7-04] Activation for multiple set point 2
Field Setting
Default
value
Range
Step
0
0/1
(OFF)
0 (A)
0/1
0
0/1
(OFF)
0
0/1
(OFF)
Unit
95