Jc" Indoor Unit: Malfunction Of Low Pressure Sensor - Daikin ERSQ 011AAV1 Service Manual

Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller

3.35 "JC" Indoor Unit: Malfunction of Low Pressure Sensor

JC
Remote Control
Display
Subcode 16
Applicable
All indoor units
Models
Method of
Malfunction is detected from pressure detected by low pressure sensor.
Malfunction
Detection
Malfunction
When the low pressure sensor is short circuit or open circuit.
Decision
Conditions
Supposed
Causes
Troubleshooting
∗1: Voltage measurement point
∗2: Refer to "Pressure Sensor", pressure/voltage characteristics table on P232.
174
Defect of low pressure sensor
Connection of high pressure sensor with wrong connection
Defect of indoor unit PC board (A4P)
Be sure to turn off power switch before connecting or disconnecting connector,
otherwise parts may be damaged.
Caution
The low
pressure sensor is
connected to X18A (blue) of
indoor unit PC board
(A4P).
YES
The
relationship
between the *1VL
and low pressure is
normal (see *2) when voltage is
measured between X18A pins
(2) and (3) indoor unit
PC board (A4P)
(see *1).
NO
Indoor unit PC boa r d A4P
GND
Microcomputer
A/D input
*2 Measu re voltage here.
NO
Bad wire connection
value < 0.1 bar
instantly
YES
Faulty sensor
value < 18 bar
over 12 minutes
+5V
Connect low pressure sensor
property and restart system.
Replace indoor unit PC board
(A4P).
Replace the low pressure sensor.
X18A
Red
4
3
Black
White
2
1
(V2809)
Troubleshooting
ESIE09-08